enquiries@collins-walker.co.uk

Collins Walker

Electric Steam & Hot Water Boilers

Tel: +44 (0) 1234 340044

Electrode Hot Water Boilers (EW)

The EW range of Electrode Hot Water boilers is available from 216 kW to 4300 kW for working pressures up to 5.5 barg dependent on the model specified.

Technical Specification – ES Boiler

Electrical Supply:

3 phase, 4 wire (415 Volt or 380Volt and frequency 50/60Hz to be specified).

Vessel:

Built to BS5500 and independently inspected by Zurich Insurance. Full certification is issued with completed boilers.

Standard Pressures:

  • Working Pressure 5.5 barg (80 psig)
  • Design Pressure 6.2 barg (90 psig)
  • Hydraulic Test Pressure 12.4 barg (180 psig)

Electrode Hot Water Boilers - Datasheet

ModelLoad Rating (kW)Maximum Current PhaseOutput (Btu/h)
EW2021530072,000
EW404386101,460,000
EW555457601,820,000
EW110109015203,650,000
EW220215030007,210,000
EW4304312600014,420,000