enquiries@collins-walker.co.uk

Collins Walker

Electric Steam & Hot Water Boilers

Tel: +44 (0) 1234 340044

Electrode Steam Boilers (ES)

The Electrode Steam Boilers in the Collins Walker range have a steam output range of 85 Kg/Hr (ES5) up to a maximum of 6,500 kg/h (ES240). Please note that the maximum output in this instance would require a 690 volt 3–phase electrical supply.

The standard steam output rating of our Electrode Steam Boiler range from a 3 phase 415 volt supply operating from and at 100°C is shown below:....

Technical Specification – ES Boiler

Electrical Supply:

3 phase, 4 wire (voltage up to 690V and frequency 50/60Hz to be specified)

Vessel:

Built to BS5500 and independently inspected by Zurich Insurance. Full certification is issued with completed boilers.

Standard Pressures:

  • Working Pressure 10.3 barg (150 psig)
  • Design Pressure 11.4 barg (165 psig)
  • Hydraulic Test Pressure 22.7 barg (330 psig)

Electrode Steam Boilers - Datasheet

ModelSteam Output (Kg/Hr)Load Rating (kW)Current Per Phase (Amps)
ES5855475
ES10170108150
ES20340215300
ES40685430600
ES901,3708601,200
ES1301,9801,2901,800
ES2403,5202,3003,200
ES48012,0007,5296,300
ES96024,00015,05812,600

Optional Extras:

  • Tank on Stand/Skid Mounted
  • Blowdown Vessel
  • Dosing Set with Pump & Tank
  • Sample Cooler
  • 3"/4" Vent Head
  • Timer Controlled Blowdown
  • PLC Controller – remote monitoring and diagnostics
  • High Pressure
  • Clean Steam – Stainless Steel

Downloads

ES240 GA Drawing

Address
Collins Walker Ltd
78 College Street
Kempston
Bedford
MK42 8LU
United Kingdom
Company No: 01087370
Copyright 2022 Collins Walker - Privacy Policy - Terms of Service